The answers we give providers and procurement teams during due diligence: power, cooling, physical security, network, and operations. Supporting logs and policies are available under NDA.

Tier III Aligned power, cooling and electrical design
N+1 Utility, UPS, generators, whips and cooling
3 × 2 MW Standby generators, automatic transfer
1,350 kW UPS capacity, expandable to 3 MW
48 hr On-site fuel, 4-hour emergency refuel SLA
10 × 42U Dedicated locked cabinets, 8 kW each
Compute

HPE ProLiant DL380a Gen12 with eight NVIDIA H200 NVL.

GPUs install directly on the motherboard over PCIe, with no risers, and sit behind enterprise-grade cooling and power delivery. Every node runs inside our own biometric cage.

Platform HPE ProLiant DL380a Gen12
GPU 8× NVIDIA H200 NVL, 141 GB each (1,128 GB GPU memory per server)
CPU 2× Intel Xeon 6745P
Memory 512 GB DDR5-6400 (16 × 32 GB)
Storage 7.68 TB enterprise NVMe, plus 960 GB mirrored NVMe boot (NS204i-u)
Network 2× 100GbE QSFP56 and 2× 10/25GbE SFP28 per server
Power 8× 2400 W Titanium hot-plug power supplies
Management HPE OneView, 3-year 24×7 support
Backbone Lumen Technologies
Power distribution

Two paths to every cabinet.

Independent A and B utility feeds run through their own transfer switches, UPS and distribution down to each cabinet. The generator plant backs both sides. Either path can fail without interrupting power.

Utility feed A Primary utility, sized for full load Utility feed B Independent second path Generator plant · N+1 2 MW 2 MW 2 MW ULSD · 48 hr on-site fuel ATS A Automatic transfer to generator ATS B Automatic transfer to generator UPS A N+1 modules, ride-through UPS B N+1 modules, ride-through 1,350 kW UPS expandable to 3 MW Busway + PDU A Overhead A-side distribution Busway + PDU B Overhead B-side distribution 01020304050607080910 8 kW8 kW8 kW8 kW8 kW8 kW8 kW8 kW8 kW8 kW Dedicated biometric cage · 10 locked 42U cabinets · A + B feed to every cabinet
A-side path B-side path Standby generation Redundant (+1) unit
Cooling, fire and fuel

Built so one failure stays one failure.

Cooling

N+1 cooling units, so a full unit can drop out without affecting thermal stability. 36-inch raised floors for airflow and continuous environmental monitoring of temperature, humidity and airflow.

Fire detection and suppression

VESDA early-warning smoke detection and clean-agent suppression integrated with HVAC. NFPA 75 and 76 aligned systems last inspected and certified by a licensed fire-protection contractor in Q2 2026.

Fuel

An active emergency refueling agreement: 4-hour response, 24/7/365, priority dispatch. Ultra-low sulfur diesel, a 48-hour on-site reserve, and fuel quality testing every six months.

Testing cadence

UPS and generators, tested on a schedule.

Every test is logged with date, technician, system, result and corrective action. Logs are retained for five years.

Interval UPS Generators
Weekly Status, alarm, log and battery temperature checks No-load start, 15 min minimum; fuel, coolant and oil pressure
Monthly Battery health scan, thermal imaging, voltage stability Fuel system, coolant, battery charger and starter
Quarterly Partial load test, component and filter inspection, firmware review ATS transfer test A→B and B→A, moderate-load exercise
Annually Full-load test with simulated failover, battery impedance testing Full-load bank test, 2 hours minimum; full electrical and mechanical inspection
Physical security

Four locked layers between the street and a GPU.

No shared cage, no shared cabinets, no co-mingled hardware. CCTV is tied to badge and biometric events, so every entry can be matched to a person and a recording. Access logs are kept for 12 months and reviewed weekly.

01
Facility entry Turnstile or mantrap with badge authentication, anti-tailgating controls, security staff on ingress. Visitors pre-authorized, ID checked, escorted at all times.
02
Dedicated cage Private to Elite-Pro. Biometric plus badge on every entry, with no shared or guest biometric profiles.
03
Locked cabinets Ten 42U cabinets locked front and rear, restricted to Elite-Pro personnel, structured cabling to prevent cross-tenant access.
04
Surveillance, 24/7 HD cameras on entrances, cage, cabinet aisles, power rooms and loading dock. Encrypted retention, monitored by the NOC.
Network

No server faces the internet directly.

Carrier

Lumen dedicated internet access over dual-path diverse fiber, with BGP routing and automatic failover between routes.

Perimeter

Redundant firewalls in a high-availability pair with IDS/IPS. Public addresses terminate here; servers stay on private networks.

Segmentation

Zero-trust separation across compute, storage, management and tenant VLANs, plus an isolated out-of-band BMC network.

Controlled exposure

External access only through NAT, reverse proxy, load balancer, VPN or API gateway, each as an approved, logged firewall rule.

Operations

People on site, and on call.

An on-site NOC watches power, cooling, network, GPU health and access events. Alerts trigger triage and, where needed, a technician dispatched to the cage.

12/5 Staffed NOC and remote hands: installs, cabling, inspections, power cycling, network patching and visitor escort.
24/7 On-call escalation outside staffed hours, with immediate cage access for critical events.
Daily Documented walk-throughs of the cage and cabinets, with weekly security reviews and a monthly full-facility inspection report.